Target granularity: 24 drive channels per PLC | Zielgranularität: 24 Antriebskanäle pro SPS | ||||
Requirements Anforderungen: | ∑-channel ∑-Kanäle: | Realization: Realisierung: | ∑-channel ∑-Kanäle: | with (∑) Gesamtbreite [cm]: |
|
---|---|---|---|---|---|
Inputs: 5 1/6 for one air drive Eingänge 5 1/6 pro Preesluftantrieb | 124 | 8x | Digitaleeingabebaugruppe SM321 DI 16 x DC24V Mlesend #6ES77321-1BH50-0AA01) | 128 | 32 |
Outputs : 1 for one air drive (0,5A@24V) Ausgänge: 1 pro air drive (0,5A@24V) | 24 | 6x | Digitalausgabebaugruppe SM 322 DO 16x UC 24/48V #6ES7322-5GH00-0AA0 | 16 | 24 |
As allready mentioned old drive control system is completely relais based according switched signals (Drive INSIDE) as well as sensor signals (EPO, EPO*,EPI, EPI*,BL, Pok). Because relais acepts loss of up to 1/3 of it's nominal voltage of 24V along of cable trace it is capable of long cable distances as graphik below shows. Because of it energia it although not sensitiv on spikes on the line. | Wie bereits erwähnt ist das alte Pressluftansteuersystem komplett relaisbasiert sowohl für Schaltsignale (DRIVE INSIDE) wie auch für Sensorsignale (EPO, EPO*,EPI, EPI*,BL, Pok). Da die Relais (2000Ω Spulenwiderstand) den Verlust von 1/3 ihrer Nominalschaltspannung über die Kabellänge tolerieren , ist alte System fähig mit recht großen Kabellängen zu leben. Aufgrund ihrer Schaltträgheit ist es auch unempfindlich gegenüber Spikes. |