User Tools

Site Tools


fair-bd:machines:sis100:technical_information:electronicroom:s5g:rackplanning:s5g

Übersicht Komponenten SIS100
★★ Übersicht der der SIS E-Räume ★★
★★★ Zurück: Sonstiges im Raum ★★★

Rackplanning of s5g (K923A.U30.134)

This BD electronic room houses 5 racks. Bauachsen: 107 - 108 (700 Uhr) U30 Blatt5220

Aufstellplan:

Racks mit hellblauem Rahmen: SD !

 E-Raum S5g-U30.134  Licht+Strom U30.134 Klima U30.134

Aufstellplan:

Schiebebalken (Window move bar)

1HE=4,45cm Auxillary tunnel
(front site view of racks)
Tunnel
wall
Accelerator
4 Zellen S51-S54: 3x cryo, 1x warm(1S52), alle Quadrupole
SD-Front: Rack1 Rack2 Rack3 Rack4 Rack5
Reih&Glied:
↓HE ⇓rad.
K0923A.U30.134#RACK105
(CPS) 230V Normal?
K0923A.U30.134#RACK104
(CPS)
K0923A.U30.134#RACK103
(CPS) & (UPS)
K0923A.U30.134#RACK102
(CPS)
K0923A.U30.134#RACK101
(CPS)230V Normal?
Niches
Schiebebalken (Window move bar)
1 Power Amplifier Exciter
“1S5DH1V.O
15 HE
2000 W

PoAmp. BTF
UPS-Steuereinheit
z.B: 3kVA/2,1kW
Power Amplifier Exciter
“1S5DH1H.I
15 HE
2000 W

PoAmp. BTF
Nische 1:
1S51.NISCHE.A100
Sektor S5ga
 Sektor S5gb
2
3 UPS-Batterieeinheit
4
5 Patchpanell Ethernet (12St.1HE)
“PP1”
BUTIS
(6 HE)
Patchpanell Ethernet (12St.1HE)
“PP1”
6 Patchpanell Ethernet (12St.1HE)
“PP2”
Patchpanell Ethernet (12St.1HE)
“PP2”
7 Patchpanell WR (8St.1HE)
“PP3”
Patchpanell WR (8St.1HE)
“PP3”
Nische 2:
1S52.NISCHE.A102
8 Patchpanell WR (8St.1HE)
“PP4”
Patchpanell WR (8St.1HE)
“PP4”
9 Libera Hadron (2HE)
LibH-1S52-5
for (“1S52DX11)”)/“1S53DX1”
“1S54DX1”/“1S55DX1”
Libera Hadron (2HE)
LibH-1S56-8
for “1S56DX1”/“1S57DX1”
“1S58DX1”/ “1S52DX22)
10
11 4x Signal Splitter Panell(1HE)
∑: 4 HE
Patchpan. (1HE)
“PP1”
Ring E↔E-Raum
4x Signal Splitter Panell(1HE)
∑: 4 HE
12
13 Nische 3:
1S53.NISCHE.A104
14
15 handle space handle space
16 Power Amplifier Exciter
“1S5DH1V.U
15 HE
2000 W

PoAmp. BTF
Power Supply Preamps DX16..8 (3HE) Power Supply Preamps DX12..4 (3HE) Power Amplifier Exciter “1S5DH1H.A
15 HE
2000 W

PoAmp. BTF
17 HV-Crate
“1S50DA0H”
CAEN SY5527,
4 HE, 600 W
6 Slots
bis zu 12 Kan./Slot

detail. Zahlen
Welche Pol.
Welche Spannung.
Floatened oder fest?
18
19 Nische 4:
1S54.NISCHE.A106
20 S53DK1
Profilgitter Auswerteeinheit:
KISS-PC (2HE)
1S53DG1
21
22 Patch Panel “PP2”
Profinet
23 electronic MegaRAD3 camera
with power supply(3HE)
control(1HE) unit
allgemeiner SPS-Platz (∑14HE):
hier speziell:


Pressluft-SPS (9HE)
“1S50DA1P”

Master-PA: autark

with 1 of 4 arms to six fold node used:

★ “1S53DAVP” (70m)
Drives nominated:
“1S53DG1”
“1S53SB1”
“1S53MP1L”


Kamera SPS
“S53MP1L”
(3 HE-Rest)
24
25 Nische 5:
1S55.NISCHE.A108
26 Industrial PC with frame graber for Screen “M53MP1L
1S52UHAIH.I.P
27
28
29 Patchpan. (1HE)
KOAX-HQ (5stk.)
30 electronic MegaRAD3 camera
with power supply(3HE)
control(1HE) unit
31 Patchpan. (1HE)
KOAX-HQ (5stk.)
Nische 6:
1S56.NISCHE.A109a
32 Patchpan. (2HE)
“Specials”
HV (5stk.)
Lemo-2P (5Stk.)
LWL (2Stk.)
Patchpan. (2HE)
“Specials”
HV (5stk.)
Lemo-2P (5Stk.)
LWL (2Stk.)
33 Power-Supply
IFC-Powernet
3HE
Supplying Cells 1S4E'5'1-4
(Straight)
34 Patchpan. (4HE)
“Steuerleitungen”
Patchpan. (4HE)
“Steuerleitungen”
35
36 Air Cooler (2HE)
37 Patchpan. (1HE)
“PP2”
Ring E↔E-Raum
Nische 7:
1S57.NISCHE.A111
38 Patchpan. (2HE)
BNC (10stk.)
RG214 (10Stk.)
reserved space:
air flow out of doupple floor
cable handling
Patchpanell (2HE)
BNC (10stk.)
RG214 (10Stk.)
reserved space:
air flow out of doupple floor
cable handling
reserved space:
air flow out of doupple floor
cable handling
39
40 reserved space:
air flow out of doupple floor
cable handling
reserved space:
air flow out of doupple floor
cable handling
41
42

Schiebebalken (window move bar)

1)
warme Zelle, kein Steerer (COFB) ABER: Knopf-BPM 1!
2)
Kopf-BPM 2