User Tools

Site Tools


ds:software:hv

This is an old revision of the document!


High Voltage Control

Common Fesa Interface

MPOD Fesa class (data type double unless noted) CAEN Fesa class GUI
Configuration data fields (for info only)
IP of the crate crateIP (e.g. 140.181.12.34) -
number of the HV channel channel (e.g. 506) -
Does the channel support only one ramp rate singleRampRate -
minimum ramp rate minRamp -
maximum ramp rate maxRamp -
resolution of the voltage measurement resVoltage -
resolution of the current measurement resCurrent -
mockup or real device (true means it is a mockup device) isMockupDevice -
Setting Property
Demanded voltage (Sollspannung) voltageS (+_min, _max) voltageS
ExpertSetting Property
current limit currentS (+_max) currentS (+_min,_max)
ramp up rate rampUpRate (+_min, _max)  rampUpRate (+_min, _max)
ramp down rate rampDownRate (+_min, _max) rampDownRate (+_min, _max)
trip time tripTime ExpertSettings tripTime
Acquisition
actual voltage (Istspannung) voltageI voltageI
actual current (Iststrom) currentI currentI
channel polarity polarity (char array: + or -) not used in the GUI, just for info purposes voltageI sollte das widerspiegeln
actual ramp up rate rampUpRateI
actual ramp down rate rampDownRateI
demanded voltage on the device (Sollpannung die auf dem Gerät gesetzt ist) setVoltageHardwareI Es gibt bei CSCO immer wieder Überlegungen, ob der Sollwert nochmal mitgeschickt werden soll. Ich persönlich finde es überflüssig, ausser vielleicht, es ist der aus dem Gerät ausgelesene Sollwert. Aber da gibt es viele Meinungen.
An/Aus des Kanals not implemented Ich glaube das sollte das powerState field in der Status property sein rh: ist es
actual trip time tripTimeI
actual current limit currentLimitI
Status
Detailed status siehe unten
Info (partly filled with the values from the configuration fields)
only one ramp rate? singleRampRate (bool)
minimum channel voltage minVoltage (queried from hardware)
maximum channel voltage maxVoltage (queried from hardware)
maximum channel current maxCurrent (queried from hardware)
minimum ramp rate minRamp
maximum ramp rate maxRamp
resolution of the voltage measurement resVoltage
resolution of the current measurement resVoltage
polarity polarity (char array: + or -)
Number of the slot the card with the channel sits in slotNumber (int32_t)
Number of the channel on a card channelNumber (int32_t)

Detailed Status Bits

In der MPOD Klasse werden momentan diese Bits ausgelesen und gesetzt. Teilweise verhalten sich die Bits nicht wie erwartet, z.B. “outputOn” zeigt nur true, wenn der Kanal eingeschaltet ist UND eine Spannung anliegt. Wenn der Kanal eingeschaltet ist aber auf 0V steht, ist das Bit false. Auf manchen Karten ist das outputAdjusting Bit immer an.

  • outputOn
  • outputInhibit
  • outputFailureMinSenseVoltage
  • outputFailureMaxSenseVoltage
  • outputFailureMaxTerminalVoltage
  • outputFailureMaxCurrent
  • outputFailureMaxTemperature
  • outputFailureMaxPower
  • outputFailureTimeout
  • outputCurrentLimited
  • outputRampUp
  • outputRampDown
  • outputEnableKill
  • outputEmergencyOff
  • outputAdjusting
  • outputConstantVoltage
  • outputVoltageBoundsExceeded
  • outputCurrentBoundsExceeded
  • outputFailureCurrentLimit

ACHTUNG: Bei den Failure Bits bedenken, dass gilt: ERROR_ON_FALSE und WARNING_ON_FALSE, d.h. bit gesetzt bedeutet alles OK!