Wiki
Wiki
This is an old revision of the document!
REMOTE POWER CYCLE:
A PLC system, designed to offer a remote power cycle for a variety of devices.
Consisting of a HMI and a IO-station in the ELR , LSB and YR Container.
IO-stations are connected by optical fiber.
An additional ethernet controller providing a HMI VNC access for the ACC network.
PLC HARDWARE:
Providing 3 IO-Station with 48 digital outputs per station and a HMI touchscreen to control the power cycle of attached devices.
CPU :
• CPU 1516-3 PN/DP - the main controller
• CP 1543-1 - for ethernet communication
IO-STATION : (3x)
• SIMATIC ET 200SP - Profinet adapter
• IM 155-6 PN HF - IO device
• DQ 8x24VDC/0.5A HF - digital output (2x)
• DQ 16x24VDC/0.5A ST - digital output [2x]
• SCALANCE XB004-2 - switch profinet/opticcal fiber
HMI :
• TP700 Comfort - 7.0'' TFT-display
PLC System Overview: