User Tools

Site Tools


hi:cooling:cooling:blmrackcooling

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
hi:cooling:cooling:blmrackcooling [2023/02/01 15:27]
p.boutachkov
hi:cooling:cooling:blmrackcooling [2023/02/01 21:10] (current)
p.boutachkov
Line 85: Line 85:
  
 Based on the estimate we need of order of 1600-1700 W cooling power. So lets use 1750 W for the search. Based on the estimate we need of order of 1600-1700 W cooling power. So lets use 1750 W for the search.
-DEC20 at __ 35 C __ ambient temperature should be able to cool down to __ 30 C __. This is a drop in replacement of a DEC15. It is 6 kg heavier than DEC15.+DEK20 at __ 35 C __ ambient temperature should be able to cool down to __ 30 C __. This is a drop in replacement of a DEK15. It is 6 kg heavier than DEK15.
  
-DEC30 can cool bellow __ 20 C __ when operated at __ 35 C __ room temperature. But it requires more space and is 80 kg+DEK30 can cool bellow __ 20 C __ when operated at __ 35 C __ room temperature. But it requires more space and is 80 kg 
 + 
 +As extreme case lest take __ 40 C __ hall temperature. The the DEK20 should stabilize the rack temperature just bellow __ 35 C __. A DEK30 unit will no have problems keeping the temperature bellow __ 20 C __ even at __ 40 C __ ambient temperature. 
 + 
 +Therefore a DEK20 is the minimum suitable choice for the rack cooling. A DEK30 is to be considered if additional BLM will be operated from the same rack.
  
 ====== Summary ====== ====== Summary ======
Line 95: Line 99:
   * The cooling power needed to control the temperature in the rack is of order of 1700 W. I expect to add 4 more units, 2 LED drivers and 2 switching matrices. The will add of order of 40 W. Hence, I use 1750 W for the estimates   * The cooling power needed to control the temperature in the rack is of order of 1700 W. I expect to add 4 more units, 2 LED drivers and 2 switching matrices. The will add of order of 40 W. Hence, I use 1750 W for the estimates
   * A DEK15 unit operating in __ 35 C __ hall temperature will stabilize the rack temperature at around __ 40 C __.   * A DEK15 unit operating in __ 35 C __ hall temperature will stabilize the rack temperature at around __ 40 C __.
-  * A DEK20 unit operating in  __ 35 C __ hall temperature will stabilize the rack temperature at around __ 30 C __. +  * A DEK20 unit operating in  __ 35 C __ hall temperature will stabilize the rack temperature at around __ 30 C __. (Note: this is a drop in replacement of DEK15, it adds 6 kg to the roof load) 
-  * A DEK30 unit can keep the rack temperature bellow __ 20 C __ even in __ 35 C __ hall.  +  * A DEK30 unit can keep the rack temperature bellow __ 20 C __ even in __ 35 C __ hall.
  
hi/cooling/cooling/blmrackcooling.1675261645.txt.gz · Last modified: 2023/02/01 15:27 by p.boutachkov