Line 25: | Line 25: | ||
{{: | {{: | ||
+ | |||
The period of oscillation changes. It is most likely related to outside temperature. | The period of oscillation changes. It is most likely related to outside temperature. | ||
- | * Switched the Tek ~MSO44 scope. The temperature in the rack is __28.3 C__ but there are no more oscillation. Seems the AC is ON all the time | + | * Switched the Tek MSO44 scope. The temperature in the rack is __28.3 C__ but there are no more oscillation. Seems the AC is ON all the time |
* Switched the CAEN HV, no HV ON. The temperature in the rack is __31 C__ | * Switched the CAEN HV, no HV ON. The temperature in the rack is __31 C__ | ||
* Switched the DAQ electronics ON. The temperature in the rack got up to __ 34.5 C __. During the night it went down to __ 33.6 C__ | * Switched the DAQ electronics ON. The temperature in the rack got up to __ 34.5 C __. During the night it went down to __ 33.6 C__ | ||
Line 32: | Line 33: | ||
{{: | {{: | ||
+ | |||
* Removed the paper " | * Removed the paper " | ||
* Removed the HV main frame, the temperature dropped from __31 C__ to __26 C __ | * Removed the HV main frame, the temperature dropped from __31 C__ to __26 C __ | ||
{{: | {{: | ||
+ | |||
* Installed the HV under the scope, above the DAQ. Turned it on. The temperature stabilized at __31.5 C __. | * Installed the HV under the scope, above the DAQ. Turned it on. The temperature stabilized at __31.5 C __. | ||
* There is a possibility to measure the HVCardsTemperature. The temperature is __ 30 C__ | * There is a possibility to measure the HVCardsTemperature. The temperature is __ 30 C__ | ||
{{: | {{: | ||
+ | |||
* Installed the HV under the DAQ in place of the NIM bin. The temperature stabilized at __ 29.5 C__. The HV card temperature is __ 29 C__. | * Installed the HV under the DAQ in place of the NIM bin. The temperature stabilized at __ 29.5 C__. The HV card temperature is __ 29 C__. | ||
{{: | {{: | ||
+ | |||
* Installed the NIM bin above the HV and the DAQ above the NIM bin. everything is on now. The temperature stabilized at __ 29.1 C __. | * Installed the NIM bin above the HV and the DAQ above the NIM bin. everything is on now. The temperature stabilized at __ 29.1 C __. | ||
Line 52: | Line 57: | ||
{{: | {{: | ||
+ | |||
The temperature was the same for both sensors. Hence there is sufficient air mixing. | The temperature was the same for both sensors. Hence there is sufficient air mixing. | ||
Line 61: | Line 67: | ||
{{: | {{: | ||
+ | |||
The outside temperature is __ 23 C__. | The outside temperature is __ 23 C__. | ||
Line 73: | Line 80: | ||
{{: | {{: | ||
+ | |||
These are the parameters of the {{ : | These are the parameters of the {{ : | ||
- | [[DEK20|files/ | + | {{ : |
Based on the estimate we need of order of 1600-1700 W cooling power. So lets use 1750 W for the search. | Based on the estimate we need of order of 1600-1700 W cooling power. So lets use 1750 W for the search. | ||
- | A DEC20 at __ 35 C __ ambient temperature should be able to cool down to __ 30 C __. This is a drop in replacement of a DEC15. It is 6 kg heavier than DEC15. | + | A DEK20 at __ 35 C __ ambient temperature should be able to cool down to __ 30 C __. This is a drop in replacement of a DEK15. It is 6 kg heavier than DEK15. |
+ | |||
+ | A DEK30 can cool bellow __ 20 C __ when operated at __ 35 C __ room temperature. But it requires more space and is 80 kg | ||
+ | |||
+ | As extreme case lest take __ 40 C __ hall temperature. The the DEK20 should stabilize the rack temperature just bellow __ 35 C __. A DEK30 unit will no have problems keeping the temperature bellow __ 20 C __ even at __ 40 C __ ambient temperature. | ||
- | A DEC30 can cool bellow __ 20 C __ when operated | + | Therefore a DEK20 is the minimum suitable choice for the rack cooling. |
+ | ====== Summary ====== | ||
+ | * The main source of heat is the CAEN HV. The heat output of the rest is much lower. | ||
+ | * Placing the HV frame under the scope has the largest effect on the cooling efficiency in the rack. | ||
+ | * The optimum configuration is with the CAEN HV at the bottom. Speculation: | ||
+ | * The cooling power needed to control the temperature in the rack is of order of 1700 W. I expect to add 4 more units, 2 LED drivers and 2 switching matrices. The will add of order of 40 W. Hence, I use 1750 W for the estimates | ||
+ | * A DEK15 unit operating in __ 35 C __ hall temperature will stabilize the rack temperature at around __ 40 C __. | ||
+ | * A DEK20 unit operating in __ 35 C __ hall temperature will stabilize the rack temperature at around __ 30 C __. (Note: this is a drop in replacement of DEK15, it adds 6 kg to the roof load) | ||
+ | * A DEK30 unit can keep the rack temperature bellow __ 20 C __ even in __ 35 C __ hall. | ||