 Based on the estimate we need of order of 1600-1700 W cooling power. So lets use 1750 W for the search. Based on the estimate we need of order of 1600-1700 W cooling power. So lets use 1750 W for the search.
-DEC20 at __ 35 C __ ambient temperature should be able to cool down to __ 30 C __. This is a drop in replacement of a DEC15. It is 6 kg heavier than DEC15.+DEK20 at __ 35 C __ ambient temperature should be able to cool down to __ 30 C __. This is a drop in replacement of a DEK15. It is 6 kg heavier than DEK15.
  
-DEC30 can cool bellow __ 20 C __ when operated at __ 35 C __ room temperature. But it requires more space and is 80 kg+DEK30 can cool bellow __ 20 C __ when operated at __ 35 C __ room temperature. But it requires more space and is 80 kg 
 + 
 +As extreme case lest take __ 40 C __ hall temperature. The the DEK20 should stabilize the rack temperature just bellow __ 35 C __.
  
 ====== Summary ====== ====== Summary ======
Line 95: Line 97:
   * The cooling power needed to control the temperature in the rack is of order of 1700 W. I expect to add 4 more units, 2 LED drivers and 2 switching matrices. The will add of order of 40 W. Hence, I use 1750 W for the estimates   * The cooling power needed to control the temperature in the rack is of order of 1700 W. I expect to add 4 more units, 2 LED drivers and 2 switching matrices. The will add of order of 40 W. Hence, I use 1750 W for the estimates
   * A DEK15 unit operating in __ 35 C __ hall temperature will stabilize the rack temperature at around __ 40 C __.   * A DEK15 unit operating in __ 35 C __ hall temperature will stabilize the rack temperature at around __ 40 C __.
-  * A DEK20 unit operating in  __ 35 C __ hall temperature will stabilize the rack temperature at around __ 30 C __. +  * A DEK20 unit operating in  __ 35 C __ hall temperature will stabilize the rack temperature at around __ 30 C __. (Note: this is a drop in replacement of DEK15, it adds 6 kg to the roof load) 
-  * A DEK30 unit can keep the rack temperature bellow __ 20 C __ even in __ 35 C __ hall.  +  * A DEK30 unit can keep the rack temperature bellow __ 20 C __ even in __ 35 C __ hall.
  