hi:cooling:cooling:blmrackcooling [2023/02/01 15:27] p.boutachkov |
hi:cooling:cooling:blmrackcooling [2023/02/01 21:03] p.boutachkov |
||
---|---|---|---|
Line 88: | Line 88: | ||
A DEC30 can cool bellow __ 20 C __ when operated at __ 35 C __ room temperature. But it requires more space and is 80 kg | A DEC30 can cool bellow __ 20 C __ when operated at __ 35 C __ room temperature. But it requires more space and is 80 kg | ||
+ | |||
+ | As extreme case lest take __ 40 C __ hall temperature. The the DEC20 should stabilize the rack temperature just bellow __ 35 C __. | ||
====== Summary ====== | ====== Summary ====== | ||
Line 95: | Line 97: | ||
* The cooling power needed to control the temperature in the rack is of order of 1700 W. I expect to add 4 more units, 2 LED drivers and 2 switching matrices. The will add of order of 40 W. Hence, I use 1750 W for the estimates | * The cooling power needed to control the temperature in the rack is of order of 1700 W. I expect to add 4 more units, 2 LED drivers and 2 switching matrices. The will add of order of 40 W. Hence, I use 1750 W for the estimates | ||
* A DEK15 unit operating in __ 35 C __ hall temperature will stabilize the rack temperature at around __ 40 C __. | * A DEK15 unit operating in __ 35 C __ hall temperature will stabilize the rack temperature at around __ 40 C __. | ||
- | * A DEK20 unit operating in __ 35 C __ hall temperature will stabilize the rack temperature at around __ 30 C __. | + | * A DEK20 unit operating in __ 35 C __ hall temperature will stabilize the rack temperature at around __ 30 C __. (Note: this is a drop in replacement of DEK15, it adds 6 kg to the roof load) |
- | * A DEK30 unit can keep the rack temperature bellow __ 20 C __ even in __ 35 C __ hall. | + | * A DEK30 unit can keep the rack temperature bellow __ 20 C __ even in __ 35 C __ hall. |